FACP IQ8Control M

ر.س50.00

Max. five micromodules, with peripheral module Part No. 772477, up to five esserbus loop modules (system supports up to 635 digital loop addresses in total)
Max. seven micromodules, with extension module Part No. 772476, up to seven esserbus loop modules (system supports up to 889 digital loop addresses in total)
Short circuit and open circuit tolerant loop operation
Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km
Up to 127 esserbus devices (fire detectors and/or manual call points)/detector zones per loop
Up to 32 esserbus transponders per loop/operation of wireless components (see chapter 10)
Operation types TM and PM as per DIN VDE 0833 – 2 to avoid unwanted alarms being triggered
Fire brigade operating panel and transmission interface on the peripheral module
Three common relays, freely programmable, monitored, floating for up to 30 V DC/1A (on the peripheral module)
TTY or RS 485 or RS 232 interface
Integration in the short circuit and open circuit resistant essernet network with up to 31 fire detection panels depends on transmission rate
Connection to graphical supervisor WINMAG via serial essernet interface (SEI)
Operating panel with alphanumerical display
Large display with 8 rows with 40 characters. As follows rated – four rows with 40 characters for the status information (first and last message), and the other four rows with 40 characters are used for system information e.g. “Sounders Off”
Event memory for up to 10,000 events
All Systems 8000 micromodules are compatible
Printer interface for internal printer
Two batteries with monitoring circuit
Monitored input for external power supply unit
Degraded mode for monitored areas up to 48,000 m² or more than 512 fire detectors acc. to the German Planning standard VDE 0833 and/or VdS 2095

Additional features for powered loop

Max. 6 powered loops and expandable up to 127 loop devices (per loop) in mixed mode / loop powered and non-loop powered (system supports up to 762 digital loop addresses in total)
esserbus-PLus (Powered Loop) supplied, synchronously controlled, acoustic alarm signaling devices as per DIN EN 54 – 3 with alarm tone as per DIN 33404
Up to 48 powered loop base sounders (Series 9200) per loop
Up to 32 powered loop IQ8Alarm / IQ8Alarm Plus devices per loop
Up to 64 powered loop IQ8Alarm Plus So / FSo devices per loop
Up to 48 IQ8Quad with alarm device per loop

SKU: logo-collection-9 Category:

Max. five micromodules, with peripheral module Part No. 772477, up to five esserbus loop modules (system supports up to 635 digital loop addresses in total)
Max. seven micromodules, with extension module Part No. 772476, up to seven esserbus loop modules (system supports up to 889 digital loop addresses in total)
Short circuit and open circuit tolerant loop operation
Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km
Up to 127 esserbus devices (fire detectors and/or manual call points)/detector zones per loop
Up to 32 esserbus transponders per loop/operation of wireless components (see chapter 10)
Operation types TM and PM as per DIN VDE 0833 – 2 to avoid unwanted alarms being triggered
Fire brigade operating panel and transmission interface on the peripheral module
Three common relays, freely programmable, monitored, floating for up to 30 V DC/1A (on the peripheral module)
TTY or RS 485 or RS 232 interface
Integration in the short circuit and open circuit resistant essernet network with up to 31 fire detection panels depends on transmission rate
Connection to graphical supervisor WINMAG via serial essernet interface (SEI)
Operating panel with alphanumerical display
Large display with 8 rows with 40 characters. As follows rated – four rows with 40 characters for the status information (first and last message), and the other four rows with 40 characters are used for system information e.g. “Sounders Off”
Event memory for up to 10,000 events
All Systems 8000 micromodules are compatible
Printer interface for internal printer
Two batteries with monitoring circuit
Monitored input for external power supply unit
Degraded mode for monitored areas up to 48,000 m² or more than 512 fire detectors acc. to the German Planning standard VDE 0833 and/or VdS 2095

Additional features for powered loop

Max. 6 powered loops and expandable up to 127 loop devices (per loop) in mixed mode / loop powered and non-loop powered (system supports up to 762 digital loop addresses in total)
esserbus-PLus (Powered Loop) supplied, synchronously controlled, acoustic alarm signaling devices as per DIN EN 54 – 3 with alarm tone as per DIN 33404
Up to 48 powered loop base sounders (Series 9200) per loop
Up to 32 powered loop IQ8Alarm / IQ8Alarm Plus devices per loop
Up to 64 powered loop IQ8Alarm Plus So / FSo devices per loop
Up to 48 IQ8Quad with alarm device per loop

details

Special colors on demand

The detectors Part No. 802271, 803271, 802371, 803371, 802373, 802374 and 803374 are approved in the scope of the DIBt system authorization for the operation with an Automatic Door System.

To determine the battery capacity of a fire alarm panel, the detector data "Quiescent current @ BMZ battery" can be added.

In order to pass through existing wires, the WAGO grips, e. g. type 243-204 (O 0.5-1 mm) or 273/104 (0.75-2.5 mm2) can be integrated into the detector base. Please use only for commissioning/maintenance of fire detectors from SW version V2.42R006 the programming software tools 8000 from version V1.05.