Common technical data:
Operating voltage
8 … 42 V DC
Quiescent current @ 19 V DC 45 μA Alarm current @ 9 V DC 18 mA No. of detector/zone 10 detectors / group; 127 detectors / ring (according to VdS) Operation indicator LED, green Alarm display LED, red and yellow flag Connection terminal max. 1,5 mm² (AWG 30-14) Application temperature
-20 °C … 70 °C
Storage temperature
-30 °C … 75 °C
Type of protection IP 66 / IP 67 Housing PC-ASA plastic Color red, similar to RAL 3020 Weight
approx. 250 g
Detector specification EN 54-11, type A Dimensions
W: 88 mm H: 88 mm D: 57 mm (with surface mount housing)

SKU: logo-collection-5 Category:

Waterproof MCP suitable for esserbus and powered loop connection, with soft address coding, alarm latch and alarm indicator. Without BUS communication, the detector operates as conventional MCP. Detector housing, surface mount housing and transparent cover are included.

The Waterproof Manual Call Point has been designed for use outdoors and in places where moisture can occur. Surface mount housing is provided with knock-out cable entries for M20 cable glands (option) for simplified installation.

Part-No.: 804961 Approval: VdS

details

Special colors on demand

The detectors Part No. 802271, 803271, 802371, 803371, 802373, 802374 and 803374 are approved in the scope of the DIBt system authorization for the operation with an Automatic Door System.

To determine the battery capacity of a fire alarm panel, the detector data "Quiescent current @ BMZ battery" can be added.

In order to pass through existing wires, the WAGO grips, e. g. type 243-204 (O 0.5-1 mm) or 273/104 (0.75-2.5 mm2) can be integrated into the detector base. Please use only for commissioning/maintenance of fire detectors from SW version V2.42R006 the programming software tools 8000 from version V1.05.

Reviews

There are no reviews yet.

Be the first to review “IQ8MCP compact IP 66 / 67, small, red, with isolator glass pane”

Your email address will not be published. Required fields are marked *